LiFePO₄ vs NMC

For a camp, van, or backup buy, the chemistry line changes three things you can check on a sheet: how many cycles are printed and to what leftover capacity, how many watt-hours the printed weight carries, and the temperature where charging stops. It does not change the watt-hours a fridge day needs. Sheets below were read 2026-11-16. Jackery and EcoFlow print NCM on the packs cited here. This URL says NMC. The handbook cited below prints NMC for the nickel-manganese-cobalt oxide. This page does not assign a nickel ratio the sheet does not print.

Planning, not a pack test. WattNeeds did not cycle a cell, weigh a station, or cold-soak one. Cycle counts below are the manufacturer's printed line, to the leftover capacity that same line names. A count to 80% and a count to 70% are different claims. A count with no leftover percent is a third claim. Usable watt-hours on this site: delivered = label × 0.90 × η. DC and USB use η = 1.00. AC outlets use η = 0.90, so the AC product is label × 0.81. That 0.90 depth is a planning factor. It is not the depth of the cycle test, and the sheets below do not print that test depth. Watt-hour math does not prove continuous watts or surge. That check is Surge traps. Use cords rated for the load; don't daisy-chain extension cords or power strips. Do not backfeed a breaker panel. A transfer switch or interlock is a licensed electrician's job.
Same calculator as the rest of the site. DoD = 0.90, buffer = 0.15, AC η = 0.90, 12 V and USB η = 1.00. Sizing up: nameplateWh = (whPerDay × days × 1.15) / (0.90 × η). Example cycle-equivalents in a year: annual Wh at the loads / (label × 0.90 × η). Years to the printed count: that count divided by the unrounded year's cycle-equivalents. Dividing the three-decimal display is a different number. Calendar aging is not inside the quotient. Round a nameplate once, with Math.round. Three-decimal displays are half-up on the full quotient.

What the cycle line actually prints

Six official lines. The first four are LiFePO4 stations. The last two print NCM. The DELTA Max extra battery is a pack that its manual says cannot be used on its own. It is in the table because it is a primary NCM sheet with a capacity, a weight, a cycle endpoint, and a charge range. It is not a power station you carry instead of a DELTA 2.

Sheet, read 2026-11-16Chemistry, as printedCycles and endpointPrinted WhPrinted weight
EcoFlow DELTA 2 manual LFP 3,000 cycles to 80%+ capacity 1,024 Wh, 51.2 V Approximately 12 kg (27 lbs)
Jackery Explorer 1000 v2 FAQ, updated 2026-10-15 LiFePO4 4,000 cycles ≥70%. This page says 70%+. 1,070 Wh Around 10.8 kg
Anker SOLIX C1000 / C1000X US page. The spec block header says C1000. The product title says C1000X. LiFePO4 3,000 cycles to 80%+ capacity 1,056 Wh 12.9 kg / 28.44 lb
BLUETTI AC180 US page. The manual spec table prints LiFePO4 and the weight, and does not print the cycle count. LiFePO4 3,500+ cycles to 80% of original capacity. The plus is not a number. Math below uses 3,500. 1,152 Wh Manual: about 16.4 kg / 36.16 lbs. The product page also prints about 16 kg / 35.27 lbs. This page divides by 16.4.
Jackery Explorer 1000 FAQ, updated 2026-08-19 Lithium-ion battery (NCM) 500 cycles. The FAQ does not print a leftover percent. This page does not add one. 1,002 Wh Around 10.6 kg
EcoFlow DELTA Max Smart Extra Battery manual NCM 800 cycles to 80%+ capacity. Shelf life on the same table: 1 year after a full charge. 2,016 Wh, 50.4 V Approximately 18 kg

A higher count with a lower leftover percent is a different sentence. 4,000 cycles to 70%+ is not "more life" than 3,000 cycles to 80%+ until someone states what happens after the test stops. 500 cycles with no percent is not "500 cycles to 80%." Retail listings that add an endpoint are not used here.

The same labels, on the site's delivered-energy check. Buffer is not inside these products. Runtime divides the unrounded product.

Label12 V / USB delivered, η = 1.00AC delivered, η = 0.90
1,002 Wh, Explorer 10001,002 × 0.90 = 901.8 Wh1,002 × 0.81 = 811.62 Wh
1,024 Wh, DELTA 21,024 × 0.90 = 921.6 Wh1,024 × 0.81 = 829.44, shown as 829 Wh
1,056 Wh, SOLIX C10001,056 × 0.90 = 950.4 Wh1,056 × 0.81 = 855.36 Wh
1,070 Wh, Explorer 1000 v21,070 × 0.90 = 963 Wh1,070 × 0.81 = 866.7, shown as 867 Wh
1,152 Wh, AC1801,152 × 0.90 = 1,036.8 Wh1,152 × 0.81 = 933.12 Wh
2,016 Wh, NCM extra battery2,016 × 0.90 = 1,814.4 WhThe pack has no AC inverter of its own. No AC product is printed here.

921.6 and 829.44, and 963 and 867, are the same products already on EcoFlow vs Jackery vs Bluetti. 1,036.8 and 933.12 match that page's AC180 row before the page rounds 1,036.8 to 1,037 and 933.12 to 933. This page keeps the unrounded products because the cycle math divides them.

Weight per watt-hour

Energy density on a station sheet is printed watt-hours divided by printed kilograms. Weight per watt-hour is the same pair turned over, in grams per watt-hour. Both include the case. On a station they include the inverter. The extra-battery row has no inverter, so its Wh/kg is not a cathode comparison against a station. Weights that say "around" or "approximately" make the quotient approximate. This is not a scale reading from this site.

Worked pair, same brand, both stations, about 1 kWh. Explorer 1000 NCM and Explorer 1000 v2 LFP.

1,002 Wh / 10.6 kg = 94.528301… → 94.528 Wh/kg

10.6 kg × 1,000 / 1,002 Wh = 10.578842… → 10.579 g/Wh

1,070 Wh / 10.8 kg = 99.074074… → 99.074 Wh/kg

10.8 kg × 1,000 / 1,070 Wh = 10.093458… → 10.093 g/Wh

99.074 − 94.528 = 4.546 Wh/kg

The unrounded gap is 4.545772…, which also rounds to 4.546. On these two "around" weights, the LFP station carries more watt-hours per kilogram. The slogan that LiFePO4 is the heavier chemistry does not survive this pair. A handbook sentence further down says LFP cells have lower energy density. The station sheet is the number a buyer can lift.

PackWh / kgShowng/WhShown
Explorer 1000, NCM, station1,002 / 10.694.52810,600 / 1,00210.579
Explorer 1000 v2, LFP, station1,070 / 10.899.07410,800 / 1,07010.093
DELTA 2, LFP, station1,024 / 1285.33312,000 / 1,02411.719
SOLIX C1000, LFP, station1,056 / 12.981.86012,900 / 1,05612.216
AC180, LFP, station, manual weight1,152 / 16.470.24416,400 / 1,15214.236
DELTA Max extra battery, NCM, no inverter2,016 / 1811218,000 / 2,0168.929

12 × 85.333… is 1,024 exactly, so 85.333 is the three-decimal display of a repeating quotient. 2,016 / 18 = 112 exactly, and the manual still says the 18 kg is approximate. 11.71875 rounds to 11.719. 12.215909… rounds to 12.216. 14.236111… rounds to 14.236. Sorting this table by Wh/kg does not sort it by chemistry. The lightest station per watt-hour in the list is the LFP v2. The heaviest station per watt-hour is also LFP. The NCM extra battery looks dense because the inverter is not in the 18 kg.

Planning estimate, not a measurement. Explorer 1000 NCM: 500 cycles with no leftover percent, 1,002 divided by 10.6 kg is 94.528 Wh/kg, and a 635.8 Wh van day reaches that 500-cycle line in 1.943 years. DELTA 2 LFP: 3,000 cycles to 80 percent or more, 1,024 divided by 12 kg is 85.333 Wh/kg, 11.914 years on the same van day. Explorer 1000 v2 LFP: 4,000 cycles to 70 percent or more, 1,070 divided by 10.8 kg is 99.074 Wh/kg, 16.599 years. The v2 sheet is 4.546 Wh/kg above the NCM sheet. Example lifetime watt-hours at 0.90 depth: 450,900, 2,764,800, and 3,852,000. An example price of 1,000 dollars is not a shelf price. Two camp days at 392 Wh name to 1,002 Wh. Charge-temperature rows checked start at 0 degrees C. Calendar aging is not in the year counts.
EXAMPLE. NCM station: 500 cycles, no leftover percent, 94.528 Wh/kg. DELTA 2: 3,000 to 80%+, 85.333 Wh/kg. v2: 4,000 to 70%+, 99.074 Wh/kg. Van day 635.8 Wh: 1.943 / 11.914 / 16.599 years to those printed counts. Two camp days name to 1,002 Wh. Charge rows checked start at 0°C.

Charging below 0°C

Every charge-temperature row checked on 2026-11-16 starts at 0°C (32°F). Discharge is allowed below that on the same sheets. A winter morning can be inside the discharge row and outside the charge row. The pack can run a load it already holds. Solar and the alternator do not refill it while the battery temperature is below the charge floor. Jackery's usage precautions say: do not charge below 0°C / 32°F. That sentence matches the model rows below. The same precautions page gives one family range for "NCM lithium battery" products and another for "LiFePO4 battery" products. Where a model FAQ prints its own range, this page uses the model row.

SheetChargeDischargeWhat the cold band means
DELTA 2 manual 0°C to 45°C (32°F to 113°F) −10°C to 45°C (14°F to 113°F) Spec floor for charge is 0°C. The troubleshooting sheet says low-temperature charging protection resumes once the battery rises above 5°C (41°F). Discharge protection on that sheet resumes above −12°C (10°F). The resume points are not the spec edges. Both documents stay. A pack between 0°C and 5°C is inside the spec charge range and can still be blocked.
Explorer 1000 NCM FAQ 0°C to 40°C −10°C to 40°C Same 0°C charge floor as the LFP v2. The top of the range is 40°C here and 45°C on the v2.
Explorer 1000 v2 FAQ 0°C to 45°C −10°C to 45°C LiFePO4 on this FAQ does not open a charge window below 0°C.
SOLIX C1000 US page 32°F to 104°F −4°F to 104°F The page prints Fahrenheit. 32°F is 0°C. (104 − 32) / 1.8 = 40, so 104°F is 40°C. (−4 − 32) / 1.8 = −20, so −4°F is −20°C. The Celsius figures are that conversion.
AC180 Manual spec row and product page: 0°C to 40°C (32°F to 104°F). FAQ Q10: avoid recharging below freezing, and prints the same 0°C to 40°C charge range. Manual spec row and product page: −20°C to 40°C (−4°F to 104°F), with a power cap in the hot end of that range. The manual's storage-and-usage bullet also says the unit can be safely charged and discharged from −20°C to 40°C. That bullet disagrees with the charging-temperature row and with FAQ Q10. This page follows the charging-temperature row and Q10. Do not charge it below 0°C on the strength of that bullet.
DELTA Max NCM extra battery 0°C to 45°C (32°F to 113°F) −20°C to 45°C (−4°F to 113°F) The charge floor matches DELTA 2. The discharge floor is colder than DELTA 2's −10°C. That is this pack's row. It is not a rule that NCM discharges colder than LFP. AC180, which is LFP, also prints −20°C on discharge.

Each manual adds the same kind of footnote: whether the product can charge or discharge depends on the battery pack's actual temperature, not the air temperature you feel. A pack that sat in a freezing van is not at cabin temperature the moment you bring it inside.

Thermal stability, stated narrowly

Both chemistries in the table are lithium-ion. The DELTA 2 manual and the NCM extra-battery manual each list over-temperature protection and low-temperature protection. That is a BMS line. It is not a measurement of a fire.

The U.S. Department of Energy's energy-storage handbook, Chapter 3, Lithium-Ion Batteries (Sandia, Preger, Torres-Castro, McDowall), is about grid storage cells, not a camping station. It says LFP has a lower average potential than other common positive electrodes, and a correspondingly lower energy density. It says LFP is more thermally stable because, unlike the metal-oxide bond in most other positive electrodes, the phosphorus-oxygen bond is strong and oxygen does not evolve during degradation. It also says NMC energy density goes up, and safety goes down, as nickel content goes up. These sheets do not print a nickel fraction, so this page does not sort the NCM packs into NMC 111 or NMC 811.

That is the sourced difference. It is a reason LFP shows up on the newer station sheets. It is not a prediction that an NCM pack fails on a normal camp trip, and it is not permission to crush, puncture, or charge a damaged LFP pack. The DELTA 2 troubleshooting sheet says that if an alarm stays on after a restart, stop using the unit and do not try to charge or discharge it. No repair steps are copied here. Watt-hours do not measure that alarm.

Storage and self-discharge

The handbook lists low self-discharge as a lithium-ion trait. It does not print an LFP percent and an NMC percent. Two Jackery FAQ rows do print a percent. They are separate from the standby-watt rows. EcoFlow's manuals checked here print a maintenance routine and do not print a percent per month. No percent is invented for them.

SheetWhat it prints for storage
Explorer 1000 NCM FAQSelf-discharge when not in use: around 5% per month. Storage temperature 0°C to 40°C. Standby power, a different row: 10 W to 15 W.
Explorer 1000 v2 FAQSelf-discharge when not in use: around 1% to 3% per month. Storage: 1 month at −20°C to 45°C, 3 months at 0°C to 45°C, 1 year at 0°C to 25°C. Standby, a different row: 18 W.
DELTA 2 manualFor long-term storage, discharge to 30% and recharge to 60% every three months. Store ideally at 20°C to 30°C. Do not store above 45°C or below −10°C for an extended period. No percent per month.
DELTA Max NCM extra batterySpec table: shelf life 1 year after a full charge. Storage range on that table: −20°C to 45°C. The maintenance section says discharge to 30% and recharge to 60% every three months, and says not to store below 14°F (−10°C) for a long time. The 14°F warning and the −20°C spec range are both in the manual. The 1-year shelf line does not replace the three-month routine. No percent per month.
AC180Manual: if unused more than 3 months, charge to 40% to 60% state of charge and store it powered off. The same note says to discharge and charge it every 3 months for battery life, and the storage section says to fully cycle it every 6 months. Product-page battery block: recharge to 40%-60% every 3-6 months. No percent per month.
SOLIX C1000 US page, FAQTurn outputs off. Check each week. If the level is below 30%, charge to 100%. Fully charge once every 3 months. No percent per month.

One month of the Explorer 1000 figure, taken as 5% of the 1,002 Wh nameplate. The FAQ says "around" and does not say whether a second month applies the percent to what remains. This page does not chain the months.

1,002 × 0.05 = 50.1 Wh in that month

1,070 × 0.01 = 10.7 Wh, and 1,070 × 0.03 = 32.1 Wh

Those are the v2 band on the same reading of the FAQ. 50.1 Wh is 50.1 / 870 = 0.057586…, shown as 0.058 of the 870 Wh home-outage day below. The top of the v2 band is 32.1 / 870 = 0.036897…, shown as 0.037 of that day. The bottom is 10.7 / 870 = 0.012299…, shown as 0.012.

Standby is a different row. 10 W × 24 h = 240 Wh. 15 W × 24 h = 360 Wh. 240 / 50.1 = 4.790419…, shown as 4.790. One day at the low end of the NCM standby row moves 4.790 times the FAQ's one-month self-discharge figure. Leave the standby watts out of the 5% line. The storage instructions are for a unit that is off.

DELTA 2's three-month routine, read as a discharge to 30% and a recharge back to 60%, moves 30 percent of the nameplate on the recharge:

1,024 × 0.30 = 307.2 Wh per visit

307.2 × 4 = 1,228.8 Wh per year of those recharges

That 1,228.8 Wh is maintenance throughput. It is not a measured self-discharge, and it is not subtracted from the 3,000-cycle line.

Illustrative cost per lifetime watt-hour

The manuals do not print a price. A shelf price seen on a product page during this read is not copied. The formula uses one example price so the denominator is the only thing that changes. The example price is $1,000. It is an input to the formula. It is not a claim about what any of these units cost.

illustrative $ per lifetime Wh = example price / (nameplate Wh × printed cycles × example DoD)

Example DoD is 0.90, the site planning factor. The sheets do not print the depth used in the cycle test. The AC180 manual's own runtime example says that unit works at 90% depth of discharge, then multiplies by 85% and adds about 15 W of self-consumption. This page does not use that runtime shortcut. The 0.90 here is not a statement that EcoFlow or Jackery cycled to 90%.

Dollars per kWh below are the per-Wh result times 1,000, then half-up to three decimals. Endpoints stay in the row. These dollars are not a ranking.

SheetWh × cycles × 0.90Lifetime Wh$1,000 / lifetime Wh, per kWh
Explorer 1000, 500 cycles, no leftover percent1,002 × 500 × 0.90450,9000.002217787 → $2.218
NCM extra battery, 800 cycles to 80%+2,016 × 800 × 0.901,451,5200.000688933 → $0.689
DELTA 2, 3,000 cycles to 80%+1,024 × 3,000 × 0.902,764,8000.000361690 → $0.362
SOLIX C1000, 3,000 cycles to 80%+1,056 × 3,000 × 0.902,851,2000.000350730 → $0.351
AC180, 3,500 of the printed 3,500+, to 80%1,152 × 3,500 × 0.903,628,8000.000275573 → $0.276
Explorer 1000 v2, 4,000 cycles to 70%+1,070 × 4,000 × 0.903,852,0000.000259605 → $0.260

Hold the example price fixed and the printed cycle count dominates the denominator. A real price ratio larger than the lifetime-Wh ratio would flip the order. The v2 row stops at 70%+, so its $0.260 is not the same test as a row that stops at 80%+. The 500-cycle row has no leftover percent, so its $2.218 is not "the cost of NCM" as a chemistry. It is this formula on that FAQ's count.

Weekend camper, 10 trips a year

Solar = 0. The day is the weekend allowance already used on under ~500 Wh: the CFX3 35 test point, 282 Wh, plus 50 Wh of lamps and 60 Wh of phone charging. 282 + 50 + 60 = 392 Wh at the loads, on 12 V and USB, η = 1.00. This page's trip is two of those days. Ten trips is this page's year. It is not a survey of how often people camp.

392 × 2 × 1.15 / 0.90 = 1,001.777… → 1,002 Wh

Steps: 784 Wh at the loads, × 1.15 = 901.6, ÷ 0.90 = 1,001.777…. One day is 392 × 1.15 / 0.90 = 500.889 → 501 Wh, the same one-day nameplate as the under-500 page. Annual energy at the loads: 392 × 2 × 10 = 7,840 Wh.

LabelCycle-equivalents / yearYears to the printed countTwo-day plan, 1,002 Wh
1,002 Wh, 500 cycles7,840 / 901.8 = 8.693724 → 8.694500 × 1,002 × 0.90 / 7,840 = 57.512755 → 57.513Rounded headroom 0. Exact headroom 1,002 − 1,001.778 = 0.222 Wh.
1,024 Wh, 3,000 to 80%+7,840 / 921.6 = 8.506944 → 8.507352.653Headroom 1,024 − 1,002 = 22 Wh.
1,070 Wh, 4,000 to 70%+7,840 / 963 = 8.141225 → 8.141491.327Headroom 68 Wh.
1,056 Wh, 3,000 to 80%+7,840 / 950.4 = 8.249158 → 8.249363.673Headroom 54 Wh.
1,152 Wh, 3,500 to 80%7,840 / 1,036.8 = 7.561728 → 7.562462.857Headroom 150 Wh.

Unbuffered runtime on the 1,002 Wh label: 901.8 / 392 = 2.300510… days, shown as 2.301 days. Hours use that unrounded quotient: (901.8 / 392) × 24 = 55.212245…, shown as 55.212 hours. 2.301 × 24 = 55.224 is the rejected chain. The unbuffered energy covers the two-day load of 784 Wh, because 901.8 is above 784. The buffer is what puts the shopping number on top of the label. A 512 Wh sheet delivers 460.8 Wh on 12 V. 460.8 is short of 784 by 323.2 Wh, and 512 is short of the 1,002 Wh plan by 490 Wh. Chemistry does not close that gap. At ten trips a year, the 500-cycle line is 57.513 years if calendar aging is zero and if each example cycle really is 90% of the label. The binding check is the 1,002 Wh nameplate, not the cathode name.

Full-time van, one day every day

The mild parked day on van daily Wh is 635.8 Wh, all on 12 V or USB in that guide: CFX3 test point 282, fan 25.2, four pucks 44, two phones 40, one laptop recharge 52.6, router ceiling 192. 282 + 25.2 + 44 + 40 + 52.6 + 192 = 635.8. Solar = 0. This page's year is 365 of those days, recharged from shore or from driving, with no alternator watt-hours subtracted. One discharge of the day's load is the assumption. It is not a logbook.

635.8 × 1.15 / 0.90 = 812.41111… → 812 Wh

635.8 × 365 = 232,067 Wh per year at the loads

LabelCycle-equivalents / yearYears to the printed countOne-day plan, 812 WhUnbuffered days
1,002 Wh, 500 cycles232,067 / 901.8 = 257.337547 → 257.3381.943Headroom 1,002 − 812 = 190 Wh901.8 / 635.8 = 1.418371 → 1.418
1,024 Wh, 3,000 to 80%+232,067 / 921.6 = 251.808811 → 251.80911.914Headroom 212 Wh921.6 / 635.8 = 1.449512 → 1.450
1,070 Wh, 4,000 to 70%+232,067 / 963 = 240.983385 → 240.98316.599Headroom 258 Wh963 / 635.8 = 1.514627 → 1.515

Hours on the 1,002 Wh label: (901.8 / 635.8) × 24 = 34.040893…, shown as 34.041 hours. 1.418 × 24 = 34.032 is rejected. On the v2 label, (963 / 635.8) × 24 = 36.351054…, shown as 36.351 hours. On DELTA 2, (921.6 / 635.8) × 24 = 34.788298…, shown as 34.788 hours.

Today's shopping number is 812 Wh on every row. A 1,002 Wh NCM label covers that day with 190 Wh of label left. The chemistry shows up in the year column. At one of these days, every day, the 500-cycle line is 1.943 years. The 3,000-cycle line to 80%+ is 11.914 years. The 4,000-cycle line to 70%+ is 16.599 years. Those years assume the example depth, a full 365 days, and no calendar aging. They are why a full-time van is the use where the printed cycle count changes the buy, and why the leftover percent still has to sit in the same sentence as the count.

If that same 635.8 Wh moved onto AC outlets, η becomes 0.90 and the divider becomes 0.81. The nameplate is 635.8 × 1.15 / 0.81 = 902.679 → 903 Wh, the van guide's all-AC day. On the 1,002 Wh label the full year quotient is 500 × 1,002 × 0.81 / 232,067 = 1.748676…, shown as 1.749 years. Multiplying the already-rounded 1.943 by 0.81 / 0.90 also lands on 1.749. Size from the full quotient. The van guide keeps this day on 12 V. The AC line is here so η = 1.00 stays on the 12 V path.

Home backup, mostly in storage

Scenario A on home outage, AC plugs only. Router 20 W × 24 h = 480 Wh. Lamps 40 W × 6 h = 240 Wh. Phones and laptops allowance 150 Wh. Total 870 Wh/day. One buffered day is 870 × 1.15 / 0.81 = 1,235.185185… → 1,235 Wh. This page's assumption is two such outage days in a year. That is not a utility statistic. Annual energy at the loads is 870 × 2 = 1,740 Wh. Battery-side draw, because η = 0.90, is 1,740 / 0.90 = 1,933.333 Wh.

LabelOne-day plan, 1,235 WhCycle-equivalents in two outage daysYears to the printed count
1,002 Wh, 500 cyclesShort by 233 Wh1,740 / 811.62 = 2.143860 → 2.144233.224
1,024 Wh, 3,000 to 80%+Short by 211 Wh1,740 / 829.44 = 2.097801 → 2.0981,430.069
1,056 Wh, 3,000 to 80%+Short by 179 Wh1,740 / 855.36 = 2.034231 → 2.0341,474.759
1,070 Wh, 4,000 to 70%+Short by 165 Wh1,740 / 866.7 = 2.007615 → 2.0081,992.414
1,152 Wh, 3,500 to 80%Short by 83 Wh1,740 / 933.12 = 1.864712 → 1.8651,876.966

Every label in that table misses one buffered outage day. The cycle-year column is hundreds or thousands of years, and the unit still does not hold the day. Chemistry does not shrink 1,235 Wh. The ~1,000 Wh class is the wrong class for this stack. That result is already on the home-outage guide and on the ~2,000 Wh page.

What does change in a closet is the storage line. Four DELTA 2 maintenance recharges move 1,228.8 Wh in a year, from the section above, against 1,933.333 Wh of battery draw in the two outage days. The maintenance visits are the same order of magnitude as the outages in this assumption. The Explorer 1000's around-5%-per-month line is 50.1 Wh in one month, which is real energy to plan to replace, and it is still smaller than one day of the 10 W standby row. The NCM extra battery's "1 year after a full charge" is a shelf line next to a three-month 30%-to-60% routine. Read both. Do not turn the shelf line into a date the pack becomes unsafe, and do not skip the three-month routine because the cycle count is 800.

Winter camping, charge floor in force

Same two camp days as the weekend section. 392 Wh/day, 12 V, η = 1.00, solar charge unavailable because the pack is below the charge-temperature row. That is this page's winter assumption for a morning in the band these sheets describe: cold enough that charging is outside the row, and, for a DELTA 2, not yet above the 5°C resume line. It is not a weather-service record.

392 × 2 × 1.15 / 0.90 = 1,001.778 → 1,002 Wh

Refill during that stretch is 0 Wh. You arrive with the two days already stored. A 1,002 Wh label meets the rounded plan with 0.222 Wh of exact headroom. A 1,024 Wh label covers it by 22 Wh. A 512 Wh label misses it by 490 Wh. Discharge can continue when the air is below 0°C and the pack is still inside the discharge row: −10°C on DELTA 2 and on both Explorer 1000 FAQs, −20°C on the AC180 discharge row and on the NCM extra battery. Below the discharge row, the sheet does not offer a runtime. The chemistry does not move the charge floor below 0°C on any row checked here. Jackery's LFP v2 and Jackery's NCM Explorer 1000 share that floor. The LFP v2's wider range is at the hot end, 45°C instead of 40°C, which is not the winter problem.

Size the cold stretch the way the rainy-weekend guide sizes a dark stretch. Keep the full load. Set days to the stretch you cannot recharge. Then read the charge row before you count on the solar input watts.

Where the chemistry changes the buy

UseWhat the chemistry line changesWhat it does not change
10 camp trips a year, 392 Wh/day, two days, 12 VAbout 7.6 to 8.7 cycle-equivalents a year. The 500-cycle line is still 57.513 years if calendar aging is zero.The buffered trip is 1,002 Wh. A 1,002 Wh label has no rounded headroom. A 512 Wh label misses by 490 Wh.
Van, 635.8 Wh every day, 12 V1.943 years on 500 cycles, 11.914 years on 3,000 to 80%+, 16.599 years on 4,000 to 70%+. The leftover percent stays attached to the count.Today's nameplate is 812 Wh. The 1,002 Wh label covers that day.
Home backup, 870 Wh/day AC, two days in the yearStorage routine, and the only printed self-discharge percents, which are Jackery's. Cycle years run to hundreds or thousands.One day names to 1,235 Wh. The ~1 kWh labels in the table miss it.
Winter, pack below the charge rowNothing in the charge floor. Every charge row checked starts at 0°C. DELTA 2's troubleshooting sheet waits until above 5°C.Two days still name to 1,002 Wh. Refill is 0 Wh until the pack is back inside the charge row. Discharge follows the discharge row.

Carry weight is a separate check from Wh/kg. A 10.6 kg station and a 16.4 kg station are different lifts even when both can hold the 812 Wh van day. Divide the printed watt-hours by the printed kilograms before treating the cathode name as the weight.

Sources

The 392 Wh day, the 635.8 Wh van day, and the 870 Wh outage day are the figures already published on under ~500 Wh, van life, and home outage. This page does not re-measure them.

Related: EcoFlow vs Jackery vs Bluetti · under ~500 Wh · ~1,000 Wh · ~2,000 Wh · weekend camping · van daily Wh · home outage · solar vs battery · surge traps

Wh calculator — one η per pass. 12 V and USB: set inverter efficiency to 1.00. AC outlets: leave η at 0.90. nameplate = (Wh/day × days × 1.15) / (0.90 × η).

Where to check pricing

As an Amazon Associate, we earn from qualifying purchases at no extra cost to you. EcoFlow, Jackery, and Bluetti partner programs are not live yet. This page does not print a shelf price. The $1,000 figure above is an example input to the lifetime formula.

Jackery — Coming soon EcoFlow — Coming soon Bluetti — Coming soon